Load Rating: 20 amps per circuit @ 120 volts (80 amps total)
Power Requirement (no load): 15 watts per circuit Surge Let-Through Voltage (6000-volt surge): 0 volts
UL 1449 Adjunct Classification Test Results:1000 surges, 6000 volts, 3000 amps, B3 pulse;Measured suppressed voltage: 170 volts; no failures.
Federal Guidelines: Grade A, Class 1, Mode 1 (CID A-A-55818)
EMI/RFI Filter, Normal Mode (50-ohm load): 40 dB @ 100 kHz; 50 dB @ 300 kHz; 50 dB @ 3 MHz; 50 dB @ 30 MHz
EMI/RFI Filter, Common Mode (50-ohm load):18 dB @ 300 kHz; 30 dB @ 1 MHz;
50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Voltage: 6000 volts (1.2 x 50 pulse, industry standard combination wave surge, as per IEEE C62.41)
Maximum Applied Surge Current:Unlimited, due to current limiting (1.2 x 50 pulse, industry standard combination wave surge, as per IEEE C62.41)
Maximum Applied Surge Energy: Unlimited, due to current limiting (1.2 x 50 pulse, industry standard combination wave surge, as per IEEE C62.41)
Endurance (C62.41-1991 Category B3 pulses): 1 kV>500,000; 3 kV>10,000; 6 kV>1000
Dimensions: 16.0" H x 12.0" W x 4.0" D (40.6 x 30.5 x 10.2 cm)
Weight: 30 lbs (13.6 kg)
Temperature Range: 5 to 35 C
Humidity Range: 5% to 95% R.H., non-condensing
Agency Listings: ETL and cETL (UL 1449, 2nd edition; CSA C22.2 No.8-M1986, R2000)